Release Notes MultiControl Version 1.8.9 (1351) Hotfix
======================================================

Date:  05/17/2024


Files:
------

MultiControl_1351.exe	PC offline tool for configuration (Windows)

NLSR1351.HEX            Controlling unit firmware

Firmware_Update.txt	Firmware update documentation (HOWTO)



Important:
----------

!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
!!                                                                      !!
!! A downgrade from 1.8.8 to 1.8.7 or lower is not suggested            !!
!! That leads to problem to problems with individual luminaire switching!!
!! configuration                                                        !!
!!                                                                      !!
!! A DOWNGRADE FROM 1.8.0 to 1.7.9 or lower is not possible due to      !!
!! changes in the file format for circuits (Version 1087).              !!
!!                                                                      !!
!! Create a backup before performing the firmware update 1.8.x.         !!
!!                                                                      !!
!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!

- ALWAYS create a backup of the control unit (NLSR) before the firmware update !

- Before performing a firmware update make sure that no system components are faulty. During the update automatic adjustments are made, which may produce undesirable results because of faulty system components.

- When the central unit is restarted all open web pages of the system must be closed !
During restart buffered information is lost and save operations will result in a partial save thus corrupting the system configuration.

- The feature GLT Gateway now requires a feature key. Without a valid key, the GLT Gateway support is disabled.
  You can request the key using your order number and serial number of the system.

- Offline-Tool default path is: %APPDATA%\Mulicontrol and %APPDATA%\Mulicontrol\ZFS



Requirements for the Web-Interface:
-----------------------------------

- The Multicontrol Web-Interface requires a modern HTML5-enabled web browser:

  - Internet Explorer 11 or higher 
  - Firefox 42 or higher
  - older Web browsers have not been tested in the release test.
    Using older versions may lead to display errors and misbehaviour of Web pages.
  - Screen resolution: 1024 x 768 or higher

changes in firmware 1.8.9 (1351):
----------------------------------------

*** General***

- NLSR2 possible as mainstation of NLSR3

- IP Filter for the communication (network security) Important: IP of the mainstation has to be registred at the substations

- After updating connected systems the IP of the master hast to be registered at all substations (Webinterface/LCD) or the communication wont work!

- We reccomend to use emergency lighting system of the muliControl series in seperated networks.

- Bugfix: Date of next function test in LCD

- Bugfix: not resetable RTC Error

- Bugfix: Email (umlauts in subject, missing symbols)

- Branding customer added


changes in firmware 1.8.8 (1344):
----------------------------------------

*** General***

- Extended mailfunctions: HTML-based Emailfunction, Representation of all important systeminformations in one Email, time-controlled -and/or event-driven transmission

- Branding added

- lower treshold for warnings of the battery temperature sensor defeatable

- icon legend added on status website

- UVC detection with customer authetification possible

- Detection of modules with customer authetification possible for all customers

- lowering of the charging voltage led by the batterie symmetry deactivated, when battery fuses get removed

- Networking reworked

- Bugfix: Error message "GLT Gateway" appears also, if the Gateway is connected via XML/IP and the communication is lost

- Bugfix building plans: lamps got shifted to (0/0)

*** LCD-Interface ***

- french special characters (,,) added

- Bugfix: schwedish special characters(,), got lost after rebooting

*** Offline-Tool ***

- offline tool now starts in the language, that was used last with it


Changes in firmware 1.8.7 (1275):
---------------------------------

*** General ***

- Bugfix: Circuit errors were logged at system startup with the wrong circuit number. The problem is solved.

- Bugfix: Lines of a mail message did not end with <CR><LF>. The consequence was no mails beeing sent (depending on the mail server). The problem is solved.

- Bugfix: E-Mail configuration page remains stuck with Busy display during "Test settings". The problem is solved.

- Bugfix: FTP connection was set up slowly or not at all and interrupted sporadically. The problem is solved.
Important: Correct gateway address setting:
Either 0.0.0.0 (no gateway) or the IP address of the router that routes the data packets to other networks.

- When the Modbus interface is activated, the Modbus registers are available via URL http://CBS_IP/modbus.xml

- Minor bug fixes


*** LCD-Interface ***

- In the Russian language, the display uses the Cyrillic character set.


*** Offline-Tool ***

- The offline tool launches in English by default.



Changes in firmware 1.8.6 (1263):
---------------------------------

*** General ***

- Bugfix: The stability of the TCP/IP stack has been improved (dead socket handling, etc.)

- Bugfix: On high network activity (web interface, equipment communication, etc.) it could happen that the control unit suddenly "froze" and stopped responding until a reboot was performed. The problem has been solved.

- Bugfix: In certain cases, the web interface was no longer available. The problem has been solved.

- In the system communication, the polling interval has been changed. The polling cycle is repeated every 10 seconds (previously 15 seconds) and the duration between polling a slave systen has been increased to 5 seconds (previously 1 second).

- In the system communication, the current time from the master station is propagated to all substations.

- The networking interface has been set to 100 MBit full duplex (before 10 MBit half duplex)


*** Web-Interface ***

- Bugfix: When printing the building plans, there was an Y-offset in the lamp position. The problem has been solved.

- A new two-column compact list is available which fits on one page without scrolling. The first half of the slave systems will appear on the left side of the table and the second half on the right side. The following screen resolutions are recommended:

  1280 x 900: 32 slave systems  (min. 1280 x 880)
  1280 x 768: 27 slave systems

- The web interface has an adjustable start page (compact list, compact two-column list, detailed list or status page). The start page is displayed when the web interface is opened or when clicking on the "overview" menu.

- Minor bug fixes



Changes in firmware 1.8.6 (1259):
---------------------------------

see Firmware 1.8.6 (1263)



Changes in firmware 1.8.6 (1219):
---------------------------------

- Support for TSM32 and TSC-UV modules

- Support for battery type OPzV

- Support for Russian language in LCD (latin characterset) and WEB

- Fault "UV connection" has been renamed to "UV connection fault".

- Bugfix: XML interface V1 and V2 contained malformed XML tags. The syntax errors have been fixed.

- Minor bug fixes



Changes in firmware 1.8.5 (1195):
---------------------------------

*** General ***

- Activation feature ist now available for vendor RP.



Changes in firmware 1.8.4 (1186):
---------------------------------

*** Hardware Requirements ***

- Control unit (NLSR) with hardware revision HW20 to HW25 have been released (HW 19 has not been released)

- The firmware is suitable for new and existing systems.


*** General ***

- Bugfix: When an automatic capacity test has been programmed on 1st. January and the test was executed after a leap year, the test would run on 31st. December. This bug has been corrected.

- Bugfix: The circuit 13 on model Mini XL has now a full configuration options (no restrictions).


*** LCD-Interface ***

- Bugfix: In menu "diagnosis > battery" the display of the battery capacity for language CZ, EN, HR, IT, PL und SE has been corrected.

- In menu "configuration > lamps" the lamp operation mode of ELS circuits is fixed and cannot be changed. The Web-Interface can be used to change the operation mode.

- Minor bug fixes


*** Web-Interface ***

- After function or capacity test an automatic BAS reset can be configured, this will simulate operation of the BAS with switching from operational to charging mode and back. The duration of the temporary charging mode is adjustable.

  This feature addresses special circumstances of electrical installations, where some lamps do not turn on correctly after a test.

- During a capacity test the actual values of the battery measurement can now be viewed on the status page.

- Minor bug fixes


*** Offline-Tool ***

- Windows 10 compatibility has been improved. The LCD simulation crashed sporadically.



Changes in firmware 1.8.3 (1150):
--------------------------------

*** Hardware Requirements ***

- Control unit (NLSR) with hardware revision HW20 to HW25 (HW 19 has not been released)

- The firmware is suitable for new and existing systems.


*** General ***

- Support for the model MiniControl XL Plus

- The TCP/IP stack library has been updated and the stability of the networking functions have been improved.

- Bugfix: The error detection for battery sensor faults (error message "bat. temp.sensor") has been revised.

- Bugfix: The internal error code is shown in brackets on log message "bat. temp. sensor".

- Minor bug fixes


*** LCD-Interface ***

- The authorization level for "Detect Modules" has been adapted to ITS # 1744.

- Bugfix: The capacity test data could be printed either on the internal or on the Centronics printer.


*** Web-Interface ***

- The menu items in the navigation menu and the page loading have been revised. The user interface is locked (half-transparent display and animated graphics) while the web browser loads a page in order to avoid incorrect user interaction.

- The feedback (circuit saved, etc.) on page "All circuits" has been revised and now occupies less resources.

- The bootloader version is displayed on page "anlage_info.html" or "support.html".

- Bugfix: On the Status page, the column "SAM" in the list of test results was determined incorrectly. The SAM inputs with the Line Monitor and TLS function were not counted correctly.

- Bugfix: When saving circuits the settings were sporadically reset to default values. The problem has been solved.

- Bugfix: On the page lamp details the result history refereed always to circuit 1 / lamp 1.

- Bugfix: The active ethernet port on page "anlage_info.html" or "support.html" was displayed incorrectly.


*** Offline-Tool ***

- (2017-08-10): On some Windows 10 systems, the simulated LCD display crashed. The problem has been solved.

- The Offline-Tool contains a demo configuration (Zip archive), which can be installed on demand.

- The Administration menu has the new page "Import / Export ...". This page contains two new features:

  - Export a lamp list in CSV format, which can be opened in a spreadsheet directly or via data import.
    The list contains following lamp data:

      circuit    (circuit number 1..96)
      lamp       (lamp number 1..20)
      position   (position text)
      mode       (lamp operation mode; maintained, non-maintained, )
      monitoring (lamp monitoring: M - lamp monitoring, CM - power monitoring, OFF - monitoring disabled)
      map        (index of the floorplan 0..99)
      x_pos      (lamp position, pixel-X-coordinate)
      y_pos      (lamp Position, pixel-Y-coordinate)

  - Import a lamp list in CSV format (see above). The function checks the format and the range of values.
    The lamp configuration is overwritten with the contents of the list. 

    Before importing, a backup of the system configuration is recommended.

    The function is intended for fast import of position text and visualization data. The lamp coordinates (x_pos, y_pos) on a map can be identified with a external graphics program (e.g. paint.net) and entered by hand into the CSV list. The placement of a large number of lamps is simplified and requires little rework in the web interface (fine placement).
    The CSV data can be processed in a spreadsheet (no Offline-Tool required).

    Recommended workflow:
	- Backup the system and import it into the Offline-Tool
	- Start the Offline-Tool and export the existing configuration (CSV) via the web interface	
    - Create a working copy of the CSV file
    - Modify working copy
    - Import working copy

    If problems arise during import or afterwards, the configuration can be restored from the backup or CSV (original data).


*** GLT Gateway ***

- Bugfix: Missing mapping for the critical circuit (0x3100 Bit 8) has been added.

- Bugfix: Missing mapping for the fan fault via IOM1.E3 (0x3102 Bit 10) has been added


*** BAT-LOGG ***

- Bugfix: When the BAT-LOGG interface had detected a wrong number of sensors, the message "BL_SENSOR_RES_0" was displayed in the LCD. The error has been corrected and "wrong sensor count" is displayed now.

- Bugfix: In LCD menu for the battery details the number of faults is now counted correctly.



Changes in firmware 1.8.2 (1109):
--------------------------------

*** Hardware Requirements ***

- Control unit (NLSR) with hardware revision HW20 or HW21 (HW 19 has not been released)

- The firmware is suitable for new and existing systems.


*** General ***

- Bugfix: Due on a CPU hardware error in the control unit, leap years between 2016 and 2031 are determined incorrectly. The date change after 28th February is now checked and corrected by software.

- Bugfix: After a firmware update luminary monitoring of all luminaries was deactivated. The problem with the data migration has been resolved.

- Minor bug fixes


*** LCD-Interface ***

- Logical circuit numbers are now using the same format "(K<terminal>)<circuit number.>" as the web-interface for 
designating circuits. For example, the terminal K1 with the logic circuit point 5 is displayed with "(K1)5".


*** Web-Interface ***

- Bugfix: The link to the system picture on the detailed list has been removed.

- Bugfix: On page Administration/E-Mail the input field "Subject" was labelled as "SMTP Server".

- The zoom levels for "zoom map in" has been increased by 8 levels in order to display large floor plans with a decent scale.


*** Offline-Tool ***

- Bugfix: On page "FTP transfer" the dialog for selection the "local path" is shown again on clicking on "Browse ...". There were problems with some web browsers.

- The data is now stored the folder "%APPDATA%/Multicontrol", where the current (logged in) user has write permission. The configuration settings are stored in %APPDATA%/Multicontrol and the "local path" defaults to %APPDATA%/Multicontrol/ZFS.

- During an active FTP transfer the display of the log file ftp.log is updated every 5 seconds.



Changes in firmware 1.8.1 (1094):
--------------------------------

!! DO NOT USE FOR UPDATES OF EXISTING SYSTEMS !!

*** Hardware Requirements ***

- Control unit (NLSR) with hardware revision HW20 or HW21 (HW 19 has not been released)


*** General  ***

- Bugfix: Circuit configuration files with the version ID 1013 and 1022 are read correctly now. The faulty data migration was caused by circuit files which were created or saved with the firmware version 1013 or 1022.

- Bugfix: In the LCD interface in the menu "Installation> Modules" and "Installing> Modules (next)" the display errors of the circuit numbers have been fixed.

- Bugfix: myControl: The issue with the test evaluation for circuit 1 has been fixed.

- Bugfix: BAT-LOGG: English error messages in the fault memory have been corrected.

- Bugfix: BAT-LOGG: Unused status flags from the interface and sensors are masked out.



Changes in firmware 1.8.0 (1087):
--------------------------------

!! DO NOT USE FOR UPDATES OF EXISTING SYSTEMS !!

*** Hardware Requirements ***

- Control unit (NLSR) with hardware revision HW20 or HW21 (HW 19 has not been released)


*** General  ***

- Bugfix: Fault "RS485 fault" had not been set during "active (on mains)".

- Support for the model myControl
  - The total current monitoring (Power Monitoring of all circuits) is not available on this model.
 
- Support for extended luminaries switching (ELS) in conjunction with the new circuit modules DCMxx-E and the new ELS-enabled
Lighting devices or lighting.

- Support for the BAT-LOGG battery monitoring (individual monitoring for each battery pack)
  - BAT-LOGG Integration in LCD and WEB
  - Support for connecting one BAT-LOGG Interface
  - Parameterization of the BAT-LOGG Interface
  - Display of the battery monitoring data on the LCD and WEB
  - Evaluation of fault messages of the interface

  Please note: On serial port COM1 either the BAT-LOGG interface or the BMS gateway may be connected. Simultaneous operation of both devices is not possible.

- Adjustable logical circuit numbers from 1 to 99.
  Each circuit has an adjustable circuit number in order to achieve a continuous logical numbering of the circuits.
  Duplicate assignments of numbers have to be checked manually.
  In the circuit configuration the selection is still based on the terminal number (K1, K2, etc.).

- In the SAM configuration each input can be assigned a function which is lighting switching (standard) or mains monitoring.
  When commissioning, this should be set first.
  The extension is needed for programming ELS-enabled circuits.

- When SAM programming in the circuit, the selected SAM address (SAM-type) determines the available SAM inputs and does not allow invalid combinations. The same applies for the operation mode/function.

- When SAM programming the name of SAM input is displayed when SAM address, SAM input and SAM operation mode (function) has been set.

- In the LCD and WEB the characters " ' & / < > can be used in text fields and do not result in an incorrect display of web interface pages.

- The circuit configuration which is stored in RAM memory is additionally secured by a checksum. When the circuit configuration is accessed, the checksum is verified and the configuration is reloaded from the file system if necessary.

- System communication: A main station with version 1.8.0 (1087) can query substations with version 1.7.x (937, 951, 955, 958, 1013, 1022, 1030, 1042). An update of substations is no longer mandatory.

- The start-up of the control unit can be interrupted (see 1.7.4).


*** LCD-Interface ***

- The BAT-LOGG integration is available via the menu "Diagnosis> Battery Monitoring".

- The SAM programming for ELS circuits can only be done via the web interface!

- The automatic battery calibration has been removed.

- Minor bug fixes and enhancements

 
*** Web-Interface ***

- Note: File names for floor plans must be written in lower case (h.png, m00.png, m01.png, etc.).

- Bugfix: Save did not work reliably and page formatting was sporadic incorrect. Both were caused by incompletely loaded content (lack of JavaScript or CSS). The internal page structure has been changed so that all content are always loaded safely.

- Bugfix: Under certain circumstances, the presentation of the circuits on the page "Administration / all circuits"  could differ from those on "Administration / circuits". The cause has been fixed.

- Bugfix: The display sequence of test results is the same as on the LCD.

- Bugfix: When transferring data from text input boxes, old entries are erased completely before new data is transferred. This prevents trailing garbage after the end of strings.

- All pages have been converted to the HTML5 standard. See supported Web browsers note!

- For the BAT-LOGG integration following pages have been created:
  - "Administration / battery monitoring"
  - "Administration / battery monitoring / settings" 
  - "Administration / battery monitoring / battery arrangement"

- The user interface has been revised and improved for easier handling:
  - new model independent logo
  - new navigation menu for quick one-click navigation
  - clear Interaction: When an operation as Save is triggered, the user interface will be locked (semi-transparent overlay and animated graphic) until the operation has completed.
  - faster page presentation by dynamic loading of page contents and partial updates of web pages.

- The page "Administration / circuits" has been revised for classic circuits modules and now is subdivided into circuit parameters, circuit SAM and lighting list.

- The selection field for circuits has moved next to the "Save" button and contains the terminal name together with the logical circuit number in parentheses (example: "K1 (1)").

- The section "circuit parameters" displays type and revision of the circuit module as well as the circuit operating parameters. The reference value for current monitoring is also shown.

- The SAM programming depends on the properties of the SAM modules (available number of inputs and adjustable features)

- Labelling of the SAM inputs is displayed in the section SAM programming

- The luminaries list is updated automatically when the number of luminaries is changed in the circuit parameters.

- The page "Administration / circuits" shows an different screen for ELS-enabled circuit modules which is subdivided into circuit parameters, circuit SAM and luminaries monitoring, lighting mode, lighting switching and lamp list.

  - Mains monitors: All SAM inputs with mains monitoring function are shown this section. The mains monitoring function for the circuit is activated by checking.
  
    Please note: A circuit module supports up to 6 entries for mains monitors & lighting switching.

  - Luminaries monitoring: The luminary monitoring for individual lamps can be turned off. This way non-existing lights are ignored during testing.

  - Lamp operation mode: The operation mode can be defined centrally for ELS-enabled lighting modules. The default settings of DIP switch are overwritten here.

  - Lighting switching: This table links SAM inputs and switched maintained lights. When a SAM input is on (E=1) the linked lights are turned on and when the input changes to off (E=0) the lamps are turned off. 
    A column may contain multiple assignments, all SAM inputs must be turned off to turn of the linked lights (logical or).
    The checkbox "all" will set or reset the entire row for a SAM input.

    Please note: A circuit module supports up to 6 entries for mains monitors & lighting switching. Linked lamps remain even if the operation mode is changed from switched maintained light to maintained or non-maintained light.

  - Lamp List: This list corresponds to the classic lamp list view. In this section the lighting mode is displayed only as set in the lamp operation mode section. A page reload may be required.

- The design of the page "Administration / All circuits" has been revised. The SAM programming uses the same display scheme as page "Administration / circuits".

  Please note: Clicking on "save system" just initiates the storage operation. While saving is in progress, the user interface in not locked. When saving is complete a message below the save button is displayed.

- The management of the substation has moved to a separate page which is accessible via the menu item "substations". If the menu item is not visible after a firmware update, open the page "options" and save. Afterwards the menu item becomes visible.

  Please note: The model myControl requires a feature key for "networking" to enable the subsystems page and menu item.

- The manual capacity test duration is now adjustable on the page "Administration / tests".

- The duration of the manual capacity test is now displayed in the caption of the button.

- Page "E-Mail" displays networking parameters (gateway, netmask, DNS) of the active Ethernet interface. The result of "test settings" is displayed without reloading the page.

- The translations of the Slovak language has been revised.

- Minor bug fixes and enhancements



Changes in firmware 1.7.9 (1042):
--------------------------------

Internal release.



Changes in firmware 1.7.5 (0122):
---------------------------------

- Hardware versions HW19, HW20 and HW21 are supported.

- A master system with version 1022 can communicate with slave system with version 1022, 1013 and 958. An update of slave systems is no longer mandatory.

- Bugfix: After a GLT gateway restart the full register update is reliably transferred. 

- Bugfix: A GLT gateway communication error was not detected, when the gateway stopped operation, after it has been detected.

- Bugfix: Error messages of modules in the system log show the correct slot number.



Changes in firmware 1.7.4 (1013):
---------------------------------

- Hardware versions HW19, HW20 and HW21 are supported.

- Booting the NLSR can be paused to create a backup of the NLSR via FTP (break boot loops). Once the text "F1" appears on the LCD boot screen on the top left corner, the key F1 must be pressed and held. When the boot process is paused the text "Paused" will appear and the settings of the active ethernet interface. Pressing F1 again will resume the boot process.
When using a connected PS/2 keyboard press (and release) the F1 key twice while booting in order to enter the paused state. Pressing F1 once will resume the boot process.

- The mains voltage measurement supports 50Hz or 60Hz (factory setting). 

- The averaging of the mains voltage measurement was increased.

- The LDM25 charger-on sequence has been revised. A invalid charge state is indicated by the LED "charge" (LED remains off, when one charger is not charging)

- A master system with version 1013 can communicate with slave system with version 1013 and 958. An update of slave systems is no longer mandatory.

- Bugfix: slave systems with unsupported firmware result in a fault "subsystem firmware" on the master system.

- Bugfix: The contact "battery operation indication during test IOM #1 K7" sporadically does not switch. The control has been revised.


*** GLT-Gateway ***

- The update interval for the GLT gateway has been increased to 15 seconds (aprox. 4 updates per minute).


- The gateway features the new register 0x30Fc "GLT gateway update counter". Its content is incremented with every data update. With this register regular data updates can be verified.

- Bugfix: The fault "GLT gateway" is set, when the communication to the GLT gateway is lost.

- Bugifx: Modbus registers for system name, system number and active ip address are filled wit h correct values.

- Bugfix: Data point "Emergency lighting blocked" is reset, when operation mode changes from "charging (off)" to "operational" during a mains failure.


*** Web-Interface ***

- The translations for Slowak language have been revised.

- Bugfix: Opening web page "plans" on systems with a large number of files in the filesystem (many circuits, many floor plans) no longer results in a timeout in the web browser.



Changes in firmware 1.7.3 (958):
--------------------------------

- Bugfix: In version 955, the stop delay on page Administration/circuits was displayed incorrectly. The value did not correspond to the configured value. The issue has been corrected.

- Bugfix #765: At system startup the configured passwords are now properly initialized.

- On the OEM page the passwords are reset to their default values by setting the checkbox "new passwords" and saving the configuration.



Changes in firmware 1.7.2 (955):
--------------------------------

- Bugfix: The number of ARP entries was increased from 20 to 40. The NLSR can thus resolve up to 40 IP addresses and implement a inter-system communication with one master station, 32 substations and seven other network devices.

- The input IOM1.E4 (closed current loop) can be used to configure a circuit shutdown of the station. The circuit shutdown is carried out when the input E=0 is permanently present. When switched off, the circuits are unpowered and function/capacity tests are locked. In the LCD the menu item "reset errors" will also terminate the shutdown after confirmation.
A running function or capacity test is terminated as soon as possible.


*** Web-Interface ***

- On page "Administration/Option" the IOM-option "functional test" is no longer available. This configuration is now done on the page "Administration/IOM" and is automatically copied from the old settings.

- Improved Windows 8 support.



Changes in firmware 1.7.1 (951):
--------------------------------

- Polish language support in LCD (complete) and Web.

- The file system can be formatted using the authorization service. 
CAUTION: Before starting, create and check a backup. In the function, the entire configuration (including OEM parameters) will be deleted!

- The authorization level maintenance has been downgraded and is now below customer. With this new level no configuration changes are possible.

- Bugfix: The messages "subsystem <n> mains" and "subsystem <n> mb" are only logged once in the master station. The fault is not logged continuously while active.

- Bugfix: The messages "subsystem <n> mains" and "subsystem <n> mb" are shown for all substations that report the status and not only for the first station.

- Bugfix: The messages "subsystem <n> mains" and "subsystem <n> mb" are generated for all stations that report the fault and not just for the first station.


*** LCD-Interface ***

- In the LCD left over help labels on the function keys have been removed.

- The labeling of the global timer control "Timer" for the function key F1 (left white key below the display) has been added.

- The LCD display errors with the global timer control were corrected


*** Web-Interface ***

- The password for accessing the web interface can be set on the OEM page and is generated according to the specifications of our OEM customers.


*** Offline-Tool ***

- The offline tool was compiled with the new runtime libraries. If the application does not start, the "Visual C + + Redistributable Package for Visual Studio 2013" can be downloaded from http://www.microsoft.com/de-de/download/details.aspx?id=40784. 
Current Windows installations have already installed the libraries.



Changes in firmware 1.7.0 (937):
--------------------------------

- Bugfix: Sending a test e-mail no longer restarts the control unit (NLSR) if the response of the mail server is too long.

- Bugfix: Lamp faults in the last circuit are now included in the message "lamps" in the system log.

- Bugfix: When starting the system circuit, fuse and earth faults are collected and logged in a single message and not individually anymore.

- Bugfix: The circuit fault on IOM #2 K1 is now correctly signaled if a lamp failure, power failure or circuit current failure (fuse, ground fault, overload) is present (OR operation).

- Bugfix: The error "battery center voltage" is signaled on the IOM 2 K4 again. In normal condition the contact K4 if off (K4 LED dark) and with active error the contact K4 is on (K4 LED lights).

- Bugfix: mains failure during a capacity test is correctly detected.

- Support for the model myControl

- Support for circuit modules DCM11 and DCM12 (myControl)

- Support for SAM24 and MC-LM. During "detect modules" the SAM module types are detected and displayed. Requirements: Z2 with HW4/HW5 and SW22 (or higher)

- Support for the charging module LDM MY (myControl)

- Support for the new LDM with HW7 and SW35 (or higher). 
  - LDM jumper setting is read and stored (reference) during "detect modules" and checked when the system starts. An incorrect LDM jumper setting results in the "LDM Jumper" fault, which is signaled acoustically and cannot be reset. 
   In older LDM the jumper setting stored as "unknown" and not checked when the system starts. 
  - Display of the LDM settings (jumper). Unknown battery type and charging current will be displayed as "-" 
  - Charging voltage reduction during of symmetry errors.  
  
- Mixed LDM revisions with old (up HW6) and new LDM (from HW7, SW35), which may result in LDM not charging the battery, are detected and displayed as "LDM versions" fault. All LDM must have either a software version of SW35 (or higher) or SW19 (or lower, SW18 is displayed as SW33).

- Revised  battery symmetry monitoring: The symmetry deviation delta_v = (V_bat + - 2 * V_Batsym) in the battery symmetry is communicated in regular intervals (about 60 seconds) to all LDM. The battery charging voltage is adjusted accordingly. 

- Adjustable error threshold for symmetry deviation (OEM page). The default deviation is set to the value 50 (+ -2.5 V).

- The external battery temperature sensor in the battery compartment is actively monitored. If the sensor does not provide readings or readings below 10C or above 50C results in a  corresponding fault. The function of the sensor (temperature readings) must be checked after a firmware update.

- Revised Swedish language (SE) for LCD and WEB.

- Variable passwords for maintenance and service (max. 8 characters). During an update to 1.7 the passwords are set to default values. 
   Note: When downgrading and upgrading all changes are lost !

- The timer control can be disabled globally (Please check, the setting after the firmware update).

- On the OEM page an expired maintenance can be configured to trigger a collective fault.

- Dates are represented in accordance with ISO8601 format YYYY-MM-DD.

- Using the Web interface the IOM output for luminary fault can be configured on IOM1 K2 or K3 IOM2. A configuration conflict with the charger fault is not checked and may not be programmed. 
   Note: If this function is used in conjunction with a MCT12/15, the charger fault must be disabled in the MCT (firmware to SW15) in the error display. On MCT with SW16 the charger fault is deactivated by default.

- Using the Web interface the IOM output charger fault can be configured on IOM1 K2 or K3 IOM2. A configuration collision with the luminary fault is not checked.

- The e-mail authorization method also supports LOGIN.

- Luminary fault and circuit current fault is forwarded to the MCT.
  Requirement: Z2 with HW4/HW5 and SW32 (or higher), MCT with SW17 or higher

- Substation faults with station number is forwarded to the MCT.
  Requirement: Z2 with HW4/HW5 and SW32 (or higher), MCT with SW17 or higher

- Configurable minimum battery voltage level for triggering a function test (OEM page).

- The settings 40 min and 320 min have been added for manual and automatic capacity test durations. (Write down the settings before the firmware update and check after the update).

- Adjustable threshold for triggering a collective fault on luminary faults: The threshold defines how many luminary faults are required to trigger a collective fault. Below the threshold there is only a message in the LCD status screen.
  The threshold can be set on the options page in the admin area via the web interface. 
  Luminary fault on the IOM is always signaled on the first error (no threshold).


*** LCD-Interface ***

- Bugfix: Display errors on the details page in menu "Test Results> capacity test" have been fixed.

- Bugfix: If no LDM are installed, the menu "Diagnosis > Modules> Charger" is now blocked and produces a beep when selected.

- The menu is entirely in Swedish language.

- Help system has been removed.

- New authorization maintenance. With the maintenance authorization, the service menu is available and allows adjustment of the maintenance date.

- For integrated circuits (Micro: circuit 7, Mini: circuit 13), the input fields for lamp and circuit monitoring have been disabled. These circuits are initialized with no lamps and no current monitoring.

- Circuits, which are not present, cannot be configured.

- A detailed view has been added to the LDM info screen which displays battery type and charging current of the LDM. "-" indicates unknown settings (LDM revision or module detection has not been updated).

- On the info screen of the LDM the details screen displays the battery type and charging current settings (jumper).

- The LDM info screen shows state "charge off", when charging has switching off due to a battery temperature >40  C.
 
- When no function or capacity test can be triggered, "test locked" is displayed on the status screen. Locking occurs on following conditions:
  - deep discharge
  - faulty battery fuse
  - low battery voltage (<230V)
  - active strong charge (LDM)
  - mains failure in an UVC (sub distribution)
  - active (mains) (modified standby) state in an UVC (sub distribution)

- Minor bug fixes and enhancements


*** Web-Interface ***

- Known bug: The settings 40 minutes and 320 minutes of the capacity test duration are not present in the web interface.

- Bugfix: On page status.xml the setting keepalive inside the http request is not evaluated anymore (python urllib2)

- Bugfix: The model name in the <title>-Tag hat been corrected.

- The language Arabic (AE) has been removed.

- Vendor specific model names are shown in the web interface.

- The page admin/anlage.html has two buttons to operate the Web-BAS in order to turn the system into "operational" or "off (charging)". The state of BAS-switch, IOM input and MCT-BAS is displayed. In order to turn the CBS "operational" all BAS-sources have to be in state "operational".
  The BAS-switch has priority over the Web-BAS and resets the Web-BAS to "operational" (BAS reset) when executing the sequence "operational -> off (charging) -> operational" on the switch.
  In case of a  NLSR (Z1) failure the system changes to "operational" 
  Requirement: Z2 with SW34 or higher 

- In the navigation the label "overview" has been replaced with the model name (e.g. Multicontrol plus).

- The page anlage_status.html has been extended with a list of all active faults in the fault memory.

- The page anlage_status.html shows more details (number of tested circuits, battery voltage, battery current) in the test overview.  

- The page anlage_status.html shows the programmed SAM functions as the number of programmed functions (text SAM has been replaced).

- On the stromkreis.html page is the state of the SAM inputs that triggered MB is shown with the configured SAM texts.

- Improved maintenance indicator: In the detailed view, and on the status page, the maintenance date along with the message "maintenance needed on"/"maintenance required since" is displayed with a background color. 14 days before the maintenance date, the background is yellow and red after expiration. In the compact view of the service message appears as a yellow dot with an exclamation mark or as a red dot (fault).

- Following has been added to the page anlage_info.html (support.html):
   - maintenance date 
   - readings of mains voltage, battery voltage, symmetry, current, temperature 
   - file system: size, used and free memory, dirty space percentage
   - BAS state in station (switch), IOM (input) and all MCT 
   - LDM jumper setting for battery type and charge current
  
- Minor bug fixes and enhancements


*** Offline-Tool ***

- Known bug: When using "scan" in the menu "detect modules" the offline tool freezes and is not usable anymore. Do not use the scan function !

- All circuit modules are shown with 6 SAM inputs, even on older circuit modules which support only 3 inputs (use the first three in that case).

- Minor bug fixes and enhancements



Changes in firmware 1.6.3 (916):
--------------------------------

- Bugfix: The periodic access of the XML Interface Version 2 no longer interferes with the configuration of the circuits (LCD / WEB) by the user.



Changes in firmware 1.6.2 (904):
--------------------------------

- Czech (CZ) language support on the LCD (complete) and Web.



Changes in firmware 1.6.1 (896):
--------------------------------

- Support for NiCd battery systems with 180 cells (1.2 V per cell). The battery center voltage tap is at 90/180 and the battery voltage range is 180-285 V.



Changes in firmware 1.6.0 (895):
--------------------------------

- Bugfix: The operation mode change of circuit 3 after a functional test has been fixed.

- Bugfix: Lamp operation modes, which were created with the firmware 862, 869 or 871 will be preserved correctly after a firmware update.

- Bugfix: The preheat ("off" or "5 minutes") is now properly preserved after a firmware update.

- Bugfix: If the repair serial number is -1, it is automatically initialized with the NLSR serial number.

- The daylight saving is set to AUTO when a default system configuration is created.

- Support for legacy circuit modules (HW1, HW2) has been improved. The supply duration and the number of SAM inputs is configured accoring to the hardware / software revision.


*** LCD interface ***

- Bugfix: When calibrating the battery current measurement, the change of the LEM sensor type becomes active immediately. The calibration can be performed without previous saving the settings.

- Bugfix: The measurement of the total current monitoring in 862 was faulty and returned bigger values.

- The LCD menu "test results > print test log" has a new option "last test", with prints the result of the last test.
 
- The information display display the hardware and software revision of a ACM, DCM, RSM, LDM in the title bar.
 
- Minor bug fixes and enhancements


*** Web interface ***

- Bugfix: The mail intervals 6h, 12h and 24h can be set and stored.

- Bugfix: After a functional test and after resetting errors emails are sent after a delay of 15 seconds or 5 minutes.

- Bugfix: Test interval "Monday, after 21 days" can be set and is not saved as "Thursday, every 28 days" anymore.

- Bugfix: The battery discharge current is displayed as a negative value.

- The presentation of the error symbols was adjusted and provides better readability for b/w printing.

- In the administration area the preheat phase can be canceld in order to shorten the test duration during service.

- In the administration area on page options a cumulative fault can be activated on mains failure and active (mains) events.

- In the administration area of the Options page, the feature keys for the XML interface and the GLT Gateway are managed (see also section "important").

- On the OEM page the maintainance date can be set.

- Minor bug fixes and enhancements


*** Offline-Tool ***

- Bugfix: A functional test, which was carried out in the offline tool, led to an incorrect display of test results. The problem is solved.

- Minor bug fixes and enhancements



Changes in firmware 1.5.4 (871):
--------------------------------

*** New Features ***

- The configuration command for DCM operation mode is logged.

- The state of the BAS on system start and state change is logged.



Changes in firmware 1.5.3 (869):
--------------------------------

*** New Features ***

- The error "battery center voltage" is signaled on the IOM 2 K4. In normal condition the contact K4 if off (K4 LED dark) and with active error the contact K4 is on (K4 LED lights).



Changes in firmware 1.5.2 (862):
--------------------------------

- Bugfix: When opening the alarm list in the web interface the NLSR does not produce a beep sequence anymore. The page opens normally.

- Bugfix: Lamp positions can be displayed with an offset to the floor plan, if the plan was scaled up or down while positioning the lamps (floorplan width  is not 1024 pixels). The problem has been solved. The lamps are positioned correctly  on the floorplans at all zoom levels.

- Bugfix: When the LEM sensor type changes in the battery current calibration menu, the new LEM parameters take effect immediately. The measurement with new calibration parameters can be performed immediately with out exiting the menu an re-entering.



Changes in firmware 1.5.1 (854):
--------------------------------

*** LCD Interface ***

- Bugfix: The key polling "hangs" for a short time when no IOM3 is connected. Problem has been solved.

- Bugfix: Faulty Testbook printout has been corrected. The language is typed out correctly.

- Bugfix: In the testbook printout menu the missing option for capacity tests has been corrected (english or croatian language).



Changes in firmware 1.5.0 (850):
--------------------------------

*** new features ***

- Support for an external battery temperature sensor. The readings are regularly monitored and displayed in LCD and WEB.

- Temperature sensor input IOM1 E2 has been removed and is not supported anymore.

- Outputs of IOM1 are mirrored on IOM3.

- FTP uploades are loggen. Data transfers to the system are reconstructable now.

- Uploaded files are automatically reloaded (during active LCD status display)

- The system number (repair serial number) can be entered on the OEM page. When replacing the NLSR the system number can be modified.

- The messages for mains failure and "active (mains)" in substations are automatically reset in the main station. No manual acknowledge (resst errors) is needed any longer.

- Preprogramming of the circuit operation mode has changed to "continuous light" (DS) for all manufacturers (according to the new documentation).
  Attention: When the system is switched to "operational" all circuits are live!

- The duration of the warmup can be set to 5 or 30 minutes.
  (For correct display the preheating in the MCT, a firmware update of the MCT is necessary.)


*** Improvements ***

- Bugfix: The new RAM of the hardware 20 is now fully utilized.

- Bugfix: DST settings were lost after a system restart.

- New permanent fan monitoring: A connected duration fan can be monitored via the input IOM1 E2 or E3, when the system is running on mains. For this, the IOM action "fan failure on E=0" or "fan failure on E=1" must be configured for the IOM input. The IOM message is used as a error message.

- New fan monitoring: A connected switched fan (IOM1 K6) can be monitored via the input IOM1 E2 or E3, when the system is running on mains. For this, the IOM action "fan K6 on E = 0 failure" or "Fan failure K6 on E = 1" must be configured for the IOM input.


*** LCD Interface ***

- Bugfix: The settings for automatic capacity test No. 2, No. 3 and No. 4 were not saved.

- The help button in the status display has been replaced with the "error" button. The left soft key now displays the contents of the fault memory.

- Expanded language support for Croatian (fully translated)

- Minor bug fixes and enhancements


*** Web Interface ***

- Bugfix: In the detailed list the display area for a system was too small, leading to a truncated representation.

- Bugfix: On the page "All circuits" the unsupported setting GMB is no longer displayed for RSM modules.

- The web interface now provides its own favorite icon that appears in the browser.

- The RP-Logos have been revised.

- New panning function: The floor plan can be moved with the mouse while holding down the mouse button. In pan active mode, the mouse cursor changes into a four-way arrow.

- New lamp positioning: When movind lamps the mouse cursor changes into a four-way arrow.

- New lamp highlighting: Selected luminaires are highlighted (background color changes) on the floor plan and the visible map section is adjusted accordingly. The function helps finding the lamps in the visualization.

- New page "administration > options": Adjustable system options have moved to a separate page.

- New Option: The function test, which is triggered by IOM1 E4, can be disabled.

- New buttons with zoom function fr floorplans and lamp symbols

- New visualization of lamps on current monitored circuits: Using the lamp operation mode "continuous light (SR)" and "readiness light (SR)" the current monitored lamps can now be visualized.

- Minor bug fixes and enhancements


*** Offline-Tool ***

- The program now has its own program icon.

- New error message, when the web server for the web-interface cannot be started.

- The file system.cfg is no longer transfered during "Upload configuration only" on page FTP transfer.

- Minor bug fixes and enhancements



Changes in firmware 1.4.3 (834):
--------------------------------

- For systems with vendor RP-Technik the authorisation "customer" is required to add circuit modules (ACM, DCM) and SAM in menu "detect modules".
Authorisation "service" was required in the past.

- Bugfix: Circuit faults are now correctly signaled on IOM #2 K1.



Changes in firmware 1.4.2 (827):
--------------------------------

- Function and capacity tests are locked while LDM operate in strong charge mode. Tests are unlocked when all LDM operate in float charge.

- LCD: Authorization in menu "diagnosis > system information > key parameters" require level service now.



Changes in firmware 1.4.1 (820):
--------------------------------

- After an Firmware-Update to version 1.4.1 following actions steps
 + In the Web-Interface open page "administration > all circuits" and click on "save system".
 + In the Web-Interface open page "administration > timer" and click on "save".
 + In the Web-Interface open page "administration > maps" select the number of maps and click on "save".

*** New Features ***

- Monitoring of a switched fan (IOM 1 K6) via input 3 of IOM 1 has been revised. The polarity of the monitoring signal is configurable via LCD and WEB.

  Important: The setting "fan failure on E=0" requires a firmware update of IOM 1 (Version: SW 3).

- Luminary faults are indicated on IOM no. 2 output K3

- XML interface for the PC-based watchdog

- The circuit configuration is cached in RAM (HW 19 up to 13 circuits, HW 20 all circuits). Accelerated access for configuration data in LCD and WEB.

- Support for NLSR hardware 20


*** Improvements ***

- Bugfix (783.3): Corrected addressing of modules in rack no. 6.

- Bugfix: The FTP server display of timestamps for files, which have been created in July, has been corrected. The bug prevented wget.exe from downloading all files.

- Bugfix: FTP server time display using the format HH:MM with leading zeros.

- Bugfix: Incomplete SAM programming (SAM "-" and/or input "-") is not transferred to the circuit module.

- Bugfix: Non-existing circuits (B-circuit on ACMx1 or DCMx1) are not evaluating when collection test results from the circuit modules.

- Improved user interface for the model MDC.

- Module detection has been accelerated.

- In the LCD and WEB the input fields for the number of luminaries are blocked for circuit module ACM and are set with default values (no lamp monitoring).

- In the LCD and WEB the input fields for number of luminaries and current monitoring are blocked set with default values (no lamp monitoring and no current monitoring).

- Current monitoring of circuits includes the lower and upper range limit. E.g.: 00W/+-5% = 95..105W (before: 96..104W)

- The threshold for a communication failure to substations has been increased to 5 minutes.

- Faults on the RS485 bus of central unit 2 are evaluated and displayed. The fault is logged and automatically reset.


*** Known Problems ***

- After a FTP transfer of configuration files to the central unit, the system has to be restarted in order to reload the new configuration files.

- Translations of WEB pages are not complete.


*** LCD Interface ***

- Bugfix: MB-messages on the last circuit have not been displayed.

- Bugfix: 783.2 LCD "calibrate c-monitor" resets the reference value of the total current monitoring.

- New menu "test results > last test" displays the test results of the last function or capacity test.

- Menu "installation > circuits" has been renamed to "installation > modules".

- Menu "diagnosis > ACM/DCM/LDM/IOM/SAM" has been renamed to "diagnosis > circuit modules".

- Menu "diagnosis > ACM/DCM/LDM/IOM/SAM > circuit modules" has been renamed to "diagnosis > modules".

- On single circuit tests earth faults of the circuits are displayed before central unit earth fault (priority).

- System test is executed, when the system has no ACM/DCM circuits.

- System test is executed on substations without battery.

- IOM messages are cleared on configuration changes and do not remain on the LCD.

- When one or more timers have been activated, the status display shows a "(T)" beside the date.

- In the menu "installation > modules" non-existing circuits are displayed as "not available" and cannot be modified.

- English terms for the system state has been revised:
    operational, off (charging), active (mains), active (battery), mains ok, mains failure, off

- Minor bug fixes


*** Web Interface ***

- Bugfix: Random restarts on page "history" when browsing test results have been fixed.

- Bugfix: When saving all circuits on page "all circuits" extra circuits were created, which could contain invalid data.

- Accelerated page rendering. Web browsers can cache static page contents (images, etc.)

- Navigation bars have been revised.

- New pages for configuring labels and visualization data (operation parameters are shown as read-only). The pages "configuration > circuits" and "configuration > maps" are enabled on page "administration" and can be reached through the URL http://192.168.5.26/cfg/anlage.html.

- Configuration of the map visualization has been revised. The number of maps not determined automatically and is specified on page "administration > maps" as well as file type and name of the map.

- Support for SVG files for visualization

- System history: capacity test data now includes "battery voltage (end)"

- The duration (minutes) of manual capacity test is shown as tooltip on the capacity test button.

- The IOM output "battery operation" during system test can be suppressed and is configured on the administration page.

- The labeling of luminaries on maps has changed. When a position text is defined for luminaries, the text is used on the map. When no text is defined, the default "system"."circuit"."lamp" ist used. The tooltip for lamps remains unchanged ("system"."circuit"."lamp"."position").

- Minor bug fixes


*** Offline-Tool ***

- Minor bug fixes


Changes in firmware 1.4.0 (783):
--------------------------------

*** New Features ***

- Each circuit supports up to 6 SAM inputs (ACM/DCM must support this).
 
- The function test features a configurable total current monitoring for the battery discharge current. When enabled following limits are possible: 5%, 10% 20% and 50%.

- Configurable e-mail notification when system faults occur.

- Optional automatic DST for time zone CET.

- Overload detection for circuit modules. When circuit modules operate above the rated current but below the fuse trigger threshold, this fault condition is detected and reported.

- luminary faults are logged with circuit and lamp number in the system log.

- Invalid circuit module types are displayed during detect modules as ***ERR and detection result cannot be saved as system configuration.

- Support for the circuit module RSM


*** General ***

Bugfix: The message "critical circuit" does not persist, when the state changes fast.

Bugfix: When for IOM inputs messages and actions are defined, messages are logged, when the action becomes active.

Bugfix: SAM inputs, which have been configured to "mb", result in a correct display in the LCD, when a MB input becomes active.

Bugfix: The FTP server does not report errors on successful data transfers, when the file size is a multiple of 512.

Bugfix: The FTP server now reports file sizes over 65536 bytes.


*** Known Problems ***

- Access speed to the file system degrades over time. When viewing test results, the problem is clearly noticeable.

- Speed ??access to the file system to deteriorate over the lifetime of the installation. 

Solution: Use the Offline-Tool for system configuration

*** LCD Interface ***

- Extended language support for French and Norwegian for status display and error messages. Configuration menus use English language.

- SAM programming of circuits now support 6 inputs.

- Minor bug fixed


*** Web Interface ***

- Page design has moved to a frameless design for faster and consistent page rendering

- Extended language support: French, Dutch, Croatian

- Page navigation: overview > "area" > "subarea" has been revised

- Page "administration > circuits" limits circuits selections to available circuits

- Page "administration > circuits" limits maps selections to available maps

- Supply duration for circuits is configured on page "administration > circuits"

- Page "administration > IOM" displays all detected IOM.

- Page "administration > SAM" displays all detected SAM.

- Total current monitoring and system test preheat is configured on page "administration > tests" 

- Page anlage_info.html displays the contents of the fault memory

- Minor bug fixes


*** Offline-Tool ***

- The Offline-Tool has been linked statically (less dependencies for external DLLs).

- The Offline-Tool now includes a web server and emulates the web interface with all functions.

- Map visualization now is available for the offline tool through the web server.

- New page "administration > FTP transfer" for simple data transfer with the system.

- The folder "C:\ZFS" can be changed on page "administration > FTP transfer"

- Errors in file handling have been fixed

- Minor bug fixes



Changes in 1.3.0 (758):
-----------------------

- After the firmware update to version 1.3.0 the calibration for battery voltage and battery center voltage in the control unit must be checked and adjusted if necessary ("installation > service > calibration"). The value for the battery voltage can be applied for battery center voltage.

*** New Features ***

- Support for the models MiniControl and MidiControl

- Support for the circuit module ACM

- Support for the GLT Gateway (MODBUS)

- Individual supply duration for each circuit during battery mode.
  Requirements: ACM V31.4.1 or higher, DCM V5.3.12 or higher

- The SAM inputs can be configured as TLS1 (E7) and TLS2 (E8) (stair lighting on demand).
  Requirements: SAM V9.2.6 or higher, Z2 V2.2.10 or higher.

- The Web features a alarm list which displays all faulty circuits and lamps including fault and position.


*** General ***

- The processing speed of the control unit and access to the local file system have been optimized. The LCD and WEB interface work significantly faster.

- Men "Installation > Service > Calibration has been revised.
  - For battery power a target value can be specified. Pressing F2 automatically determines the zero point correction (offset). The scale correction must be manually set to 0.
  - For battery voltage a target value can be specified. Pressing F2 automatically determines the zero point correction (offset) and Scale correction.
  - The scale resolution for battery voltage has been increased (factor 4). During firmware update the scale is automatically adjusted.
  - The menu for battery symmetry is unchanged. The scale from battery voltage can be used here.

- Isolation fault has been renamed to earth fault.

- The printout of the capacity test has been revised.

- The maintenance reminder appears 14 days before expiration as a message in the status line.

- When reading of test results of a specific date the last test of the day is returned (before it was the first test).

- Bugfix: Time of battery current measurement during the function test has been correctet.

- Bugfix: Test resultes in LCD and WEB are stored in seperated variables.


*** LCD Interface ***

- (600.5): The display of manual and automatic test results has been extended. System faults are displayed now (earth fault, deep dischage, etc.).

- (665.7): Menu "configuration > network > ip addresses" saves changes, when changes were made.

- F6 on the PS/2 keyboard opens the menu "konfiguration > administration > ip addresses"

- (665.6): During input of texts a inactivity timeout is active now.

- (665.5): The status of UV-C #1 is evaluated in diagnosis.

- In the Menu "diagnosis > DMC/LDM/IOM/SAM > SAM/IOM inputs" the middle function button F2 has been labeld with "update". The button reads the inputs of SAM and IOM.

- A manual function test is blocked, if one charger operates in strong charge. Pressing the middle function button is acknowledged by a beep.

- The menu "detect modules" has been revised. When entering the menu the stored detection results are displayed. Depending on the autorisation (customer, service) following modules are detected when pressing the middle function button (F2):

  - customer: only SAM are detected
  - service:  ACM/DCM/IOM/SAM are detected

- Currents faults (current monitoring) are not shown as circuit faults anymore. Circuit faults are triggerd by earth fault or a broken fuse.

- A mains failure in a monitored substation triggers a fault (system is not running in battery mode).

- Battery current and voltage are displayed in the test results.

- Battery temperature has been removed in "diagnosis > battery".


*** web interface ***

- The circuit page has been revised. Infomations has been added and restructured.

- Pictures of lamps has been corrected and extended (DO, KB, KE, VM).

- The navigation bars in the adminstration area have been revised.

- Translation issues have been fixed.

- Maps for the flourplan visualisation can be stored on an external storage system (e.g. web server, NAS, etc. by adding a storage path. 

- Karten der Grundrissvisualisierung knnen mit einem Prefix versehen werden, um diese auf einem anderen Speicherort zu legen (z.B. Web-Server, NAS, usw.). Using the external path, even very large maps can be visualized, which would not fit into the local file system.

- The display of canceld tests has been improved. Test results which has not been gatherd (battery parameters, circuit state, lamp state) are not shown anymore.

- Battery temperature has been renamed into system temperature (temperature sensor is inside the control unit).

- Circuit administration: The button for reseting the current monitor reference value is named "Reset".


*** Offline-Tool ***

- Bugfix: The functions for reading and writing configuration files have been revised.

- New command line option for setting the srorage location C:\ZFS\ (max. 112 chars)


Changes in 1.2.3 (639):
-----------------------

Internal Release


Changes in 1.2.2 (628):
-----------------------

*** General ***

- (600.2): The FTP server's system type has been changed to UNIX. Path handling and folder support has been improved.

- Bugfix (600.6): Log messages with UVC faults now include the UVC's slot number (84=UVC 1, 85=UVC 2, usw.).

- Bugfix (600.1): The reoccuring L1/L2/L3/N fault after the system's mains connection has been corrected without a system reset has been fixed.


*** LCD Interface ***

- (600.5): The display of manual and automatic test results now includes system faults (ISO fault, deep discharge, etc.).


*** web interface ***

- Inside the test history the circuit state is displayed using traffic light notaion (red/green).

- The display of isolation faults detected by the central unit and the DCM has been corrected.

- A link to the current log file has been added to the status page.

- Bugfix (600.7): Manual capacity tests can be run using the button "capacity test".

- Bugfix (600.4): System tests are no longer affected by an active status page oder by viewing test results.



Changes in 1.2.1 (600):
-----------------------

*** General ***

- Detection threshold for battery discharge changed from 3 to 10 successive errors.

- On battery discharge the battery current is logged as well.

- During system test the contact K2 on IOM #2 becomes active.


*** LCD Interface ***

- Bugfix (592.11): When programming MC-LM inputs the function is set automatically.

- Bugfix (592.10): Entering values for circuits, time and date values inside the timer programming menu (LCD-If) is working again. The lower limit for circuit values during range adjust has been corrected.

- Bugfix (592.9): Minor corrections in the English menu structure.

- Bugfix (592.1): The display of detected modules inside the menu "detect modules" has been corrected.

- The configuration of circuits begins with the first installed (detected) circuit.


*** web interface ***

- Bugfix (592.14): The circuit type is now displayed on page admin/stromkreis_index.cgi and admin/config.cgi.

- Bugfix (590.1): On page admin/anlage_index.cgi the column header "status query" has been renamend into "cumulative error".

- The max. number of circuits is now model depended (Multi-Control, Micro-Control) on page admin/config.cgi and admin/timer_index.cgi.

- Fuse faults during the last function test are displayed in stromkres_index.cgi.



Changes in 1.2.0 (592):
-----------------------

- After a firmware update from V1.0.0 to 1.1.x/1.2.x the function "installation > detect modules" must be executed in the central unit.

*** General ***

- Bugfix (496.17): Queries of deactivates circuits and luminaries are omitted.

- Bugfix (496.15): During function test the battery voltage and battery center voltage is stored after the first half of the function test.

- Bugfix (496.8): Tests are disabled, when one LDM is in strong charge mode.

- Bugfix (496.7): The fan is turned on, when one LDM is in strong charge mode.

- New intersystem communication via TCP/IP, where the main system gathers and evaluates status information from up to 10 subsystems over the network. Optional connection monitoring of subsystems and error forwarding to the main system is available.

When activating or deactivating the communication or adding and removing ip addresses the system requires a reboot.

- changed IOM output assignments: circuit error event has moved to IOM No. 2 K1. The modified-standby event has moved to IOM No. 1 K3.

- Modified-standby events of SAM inputs are shown in the status display and logged.

- New SAM function for switched standby luminaries. This function switches standby luminaries without (turned off) delay. A firmware update on central unit 2 and all DCM is required too.

- Simplified programming of the line-monitor. The setting "MC-LM" in the input selection is used now.

- Predefined texts for SAM and IOM inputs.

- Active critical circuit loop triggers the display "critical circuit" in the status display.

- Faults during function tests are categorized into circuit fault, luminaire fault (luminaire monitoring), current fault (current monitoring)

- DCM31, DCM41 and DCM61 support

- MicroControl support

- minor bug fixes

*** LCD Interface ***

- Bugfix (496.9): The current value on the LDM info pages is scaled correctly now.

- Bugfix (496.5): Single DCM test now displays ISO faults.

- Bugfix (496.1): The screen in the menu "installation > lamps" is updated completely on changes.

- "diagnosis > DCM/LDM/IOM/SAM > SAM/IOM inputs" displays input states which trigger modified-standby as "M".

- changes in menu structure:

 * The menu item "installation > key parameters" moved to "diagnosis > system information

* The menu items "diagnosis > circuits", "diagnosis > chargers", "diagnosis > SAM/IOM inputs" have moved into a new sub menu "diagnosis > DCM/LDM/IOM/SAM"

* The menu item "configuration > administration > network" has moved to "configuration > administration > network > ip addresses".

 * The menu item "configuration > administration > E-mail" has moved into "configuration > administration > network"

* Authorisation for the menu items "installation > detect modules", ""configuration > timer", "configuration > administration > IOM inputs" and ""configuration > administration > SAM inputs" has changes to level customer.

- new menus:

* The menu item "diagnosis > subdistribution" supports error tracking for UV-controllers. Mains failure and faults are displayed and updated frequently.

* The menu item "diagnosis > substation" displays status and fault memory of networked sub systems.

* The menu item "reset errors > show errors" displays the contents of the fault memory.

 * The menu item "installation > calibrate circuits" initiates a special manual function test which determines the reference value for current measurements for all circuits.


*** web interface ***

- Bugfix (496.4): The button "history" displays the last test, when no or an invalid date has been entered.

- Bugfix (496.3): In the modifed-standby state no function or capacity tests can be initiated through the web interface.

- The new configuration page for all circuits allows fast configuration of circuit position, number of monitored luminaires, current monitoring, circuit operation mode and SAM settings.

- anlage_info.cgi has been revised

- revised display of system faults

- revised localization.

- revised logos.

- improved stability


*** Offline tool (PC Configuration software) ***

- print function (to file) for the system configuration in C:\ZFS using the CSV format. All configuration must be transferred to the PC first.


Changes in 1.1.0 (486):
-----------------------

- After a firmware update from V1.0.0 to 1.1.x/1.2.x the function "installation > detect modules" must be executed in the central unit.

- Release 1.1.0: For correct function of the timer a firmware update of all DCM is required. Otherwise the DCM will malfunction when the timer switches circuits during modified-standby or delay.


-----

Abbreviations:

Bugifx: correction
PnP:    plug and play
LCD-If: LCD interface
Web-If: web interface